2 Parameters
2.2 List of parameters
SINAMICS G130/G150
452
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the minimum time for a transition from open-loop controlled to closed-loop controlled operation after the lower
changeover speed p1755 * (1 - p1756 / 100 %) has been exceeded.
Dependency:
Refer to: p1755, p1756
Note:
With p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only (changeover for p1755).
Description:
Sets the proportional gain Kp of the controller for speed adaptation with encoder
Description:
Sets the integral-action time Tn of the controller for speed adaptation with encoder
Description:
Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PMSM):
Displays the system deviation for speed adaptation.
r1762[0]: Angular deviation [rad-el] of the estimated EMF.
r1762[1]: Angular deviation [rad-el] of the low-level signal response for pulse technique.
Index:
[0] = Deviation model 1
[1] = Deviation model 2
p1759[0...n]
Motor model changeover delay time open/closed-loop control / MotMod t op_cl
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
2000 [ms]
0 [ms]
p1760[0...n]
Motor model with encoder speed adaptation Kp / MotMod wE n_ada Kp
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 100000.000
1000.000
p1761[0...n]
Motor model with encoder speed adaptation Tn / MotMod wE n_ada Tn
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
1000 [ms]
4 [ms]
r1762[0...1]
Motor model deviation component 1 / MotMod dev comp 1
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6721, 6730,
6731
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......