2 Parameters
2.2 List of parameters
SINAMICS G130/G150
578
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
Refer to: p2291
Description:
Sets the signal source for the minimum limiting of the technology controller.
Dependency:
Refer to: p2292
Description:
Sets the signal source for the offset of the output limiting of the technology controller.
Description:
Setting to invert the system deviation of the technology controller.
The setting depends on the type of control loop.
Value:
0:
No inversion
1:
Inversion
Caution:
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note:
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
2291[0]
p2298[0...n]
CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
2292[0]
p2299[0...n]
CI: Technology controller limit offset / Tech_ctrl lim offs
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p2306
Technology controller system deviation inversion / Tec_ctr SysDev inv
VECTOR_G
(Tech_ctrl)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......