2 Parameters
2.2 List of parameters
SINAMICS G130/G150
438
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the denominator damping for current setpoint filter 2.
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description:
Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description:
Sets the numerator damping for current setpoint filter 2.
Dependency:
Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
Description:
Sets the speed actual value filter 5 as low pass (PT2) or general 2nd order filter.
Value:
1:
PT2 low pass
2:
General 2nd order filter
Dependency:
The speed actual value filter is activated via p1656.4 and parameterized via p1677 ... p1681.
Note:
For a general 2nd order filter, by inserting the same natural frequency in both the numerator and in the denominator,
i.e. bandstop frequency, a bandstop filter is implemented. If the numerator damping of zero is selected, the bandstop
frequency is completely suppressed.
The denominator damping can be determined from the equation for the 3 dB bandwidth:
f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
p1664[0...n]
Current setpoint filter 2 denominator damping / I_set_filt 2 D_den
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 10.000
0.700
p1665[0...n]
Current setpoint filter 2 numerator natural frequency / I_set_filt2 fn_num
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.5 [Hz]
16000.0 [Hz]
1999.0 [Hz]
p1666[0...n]
Current setpoint filter 2 numerator damping / I_set_filt 2 D_num
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 10.000
0.700
p1677[0...n]
Speed actual value filter 5 type / n_act_filt 5 type
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
4715
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 2
2
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......