4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1886
List Manual (LH2), 07/2016, A5E03263479A
Reaction upon F:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A35223 (F, N)
TM: Zero mark offset not permissible
Message value:
%1
Message class:
Application/technological function faulted (17)
Drive object:
B_INF, TM31, VECTOR_G
Component:
None
Propagation:
BICO
Reaction:
NONE
Acknowledge:
NONE
Cause:
The entered zero mark offset is not permissible.
Alarm value (r2124, interpret decimal):
1: Zero mark offset is too high.
Remedy:
Enter the zero mark offset in the permissible range (p4426).
Reaction upon F:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F35230
TM: Hardware fault
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, TM120, TM150, TM31, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
GLOBAL
Reaction:
Vector: NONE
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
POWER ON
Cause:
The Terminal Module (TM) used has signaled internal errors.
Signals from this module may not be evaluated because they are very likely to be incorrect.
Remedy:
If required, replace the Terminal Module.
F35233
DRIVE-CLiQ component function not supported
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, TM120, TM150, TM31, VECTOR_G
Component:
Terminal Module (TM)
Propagation:
BICO
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: Terminal Module 31 does not support the function "Timer for temperature evaluation" (X522.7/8, p4103 > 0.000).
4: The improved actual value resolution is not supported (p4401.4).
5: The improved setpoint resolution is not supported (p4401.5).
6: The residual value handling in the setpoint channel cannot be deactivated (p4401.6).
7: Output frequencies greater than 750 kHz cannot be activated (p4401.7).
Remedy:
For fault value = 1:
- Deactivate timer for temperature evaluation (X522.7/8) (p4103 = 0.000).
- use Terminal Module 31 and the relevant firmware version to enable the "Timer for temperature evaluation" function
(Article No. 6SL3055-0AA00-3AA1, firmware version 2.6 and higher).
See also: p4103
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......