SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1003
2 Parameters
2.2 List of parameters
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9871.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9871.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9871.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9871.4 =
1).
0024 hex:
Extended functions without selection are enabled (permissible for r9871.16 = 1).
0025 hex:
Extended functions without selection and basic functions via onboard terminals are enabled (permissible for r9871.16
= 1).
0040 hex:
Basic functions are enabled via TM54F
0041 hex:
Basic functions are enabled via TM54F and basic functions via onboard terminals.
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change always becomes effective only after a POWER ON. Exception: Changes to p9801.0 become effective
immediately.
MM: Motor Module
SI: Safety Integrated
SMM: Safe Motion Monitoring
STO: Safe Torque Off / SH: Safe standstill
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
F-DI: Failsafe Digital Input
F-DO: Failsafe Digital Output
Description:
Sets the enable signal for the "Safe Brake Control" function (SBC) on the Motor Module.
0: Inhibit SBC
1: Enable SBC
Dependency:
Refer to: p9602
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The "Safe Brake Control" function is not activated until at least one safety monitoring function has been enabled (i.e.
p9501 not equal to 0 and/or p9801 not equal to 0).
It does not make sense to parameterize "no motor holding brake available" and enable "Safe Brake Control" (p1215
= 0, p9602 = p9802 = 1) if there is no motor holding brake.
The parameterization "motor holding brake the same as sequence control, connection via BICO" and "Safe Brake
Control" enabled (p1215 = 3, p9602 = 1, p9802 = 1) is not practical.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO (SH) via terminals (MM) enable
Enable
Inhibit
2810
02
Enable motion monitoring functions
integrated in drive (MM)
Enable
Inhibit
-
03
Enable PROFIsafe (MM)
Enable
Inhibit
-
05
Enab motion monit functions integr in drive
w/out selection (MM)
Enable
Inhibit
-
06
Basic functions via TM54F
Enable
Inhibit
-
p9802
SI enable Safe Brake Control (Motor Module) / SI enable SBC MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
-
Func. diagram:
2814
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......