2 Parameters
2.2 List of parameters
SINAMICS G130/G150
180
List Manual (LH2), 07/2016, A5E03263479A
For bit 29:
When the bit is set, the EnDat encoder is initialized under a certain velocity and, therefore, with high accuracy. If
initialization at a higher velocity is requested, fault F31151, F32151, or F33151 is output.
For bit 31:
When monitoring is active, the levels of the individual track signals and the corresponding inverted track signals are
monitored separately.
Description:
Sets the filter time for a squarewave encoder.
The hardware of the squarewave encoder only supports the following values:
0: No filtering
0.04 µs
0.64 µs
2.56 µs
10.24 µs
20.48 µs
Dependency:
Refer to: r0452
Notice:
If the filter time is too long, the track signals A/B/R may be suppressed and the appropriate messages output.
Note:
The most suitable filter time depends on the number of pulses and maximum speed of the square-wave encoder.
The filter time is automatically corrected to the next value when entering a non-specified value. In this case, no
message is output.
The effective filter time is displayed in r0452.
Description:
Sets the ramp-up time for the encoder.
The encoder supplies stable track signals once this time has elapsed.
Notice:
This parameter is automatically preassigned for encoders from the encoder list and for identify encoder (p0400).
Description:
Copies the actual serial number of the encoder belonging to this Encoder Data Set (EDS) to p0441 ... p0445.
Example:
For p0440[0] = 1, the serial number of the encoder belonging EDS0 is copied to p0441[0] ... p0445[0].
Value:
0:
No action
1:
Transfer serial number
Dependency:
Refer to: p0441, p0442, p0443, p0444, p0445, r0460, r0461, r0462, r0463, r0464, p1990
p0438[0...n]
Squarewave encoder filter time / Enc t_filt
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
100.00 [µs]
0.64 [µs]
p0439[0...n]
Encoder ramp-up time / Enc ramp-up time
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
65535 [ms]
0 [ms]
p0440[0...n]
Copy encoder serial number / Copy enc ser_no
VECTOR_G, ENC
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......