2 Parameters
2.2 List of parameters
SINAMICS G130/G150
228
List Manual (LH2), 07/2016, A5E03263479A
Description:
The inhibit list contains parameters that should be withdrawn from the automatic motor and closed-loop control
parameter calculation (p0340, p0578).
Value:
0:
No parameter
600:
Motor temperature sensor
640:
Current limit
1082: Maximum speed
1460: Speed controller P gain
1462: Speed controller integral time
1470: Speed controller P gain encoderless
1472: Speed controller integral time encoderless
1520: Torque limit upper/motoring
1521: Torque limit lower/regenerative
1530: Power limit motoring
1531: Power limit regenerative
1590: Flux controller P gain
1592: Flux controller integral time
2141: Speed threshold 1
2142: Hysteresis speed 1
Note:
p0570 defines the number of entries (starting at index 0) for which the inhibit should apply. p0572 can be used to
define for which drive data sets the inhibit list should apply.
If a motor data set is entered into a parameter number, then this is not overwritten as soon as only one drive data set
refers to the motor data set (p0186).
Description:
Setting for activating/deactivating the inhibit list.
Depending on the setting, the parameters of the inhibit list (p0571) should be overwritten when calculating the motor
and closed-loop control parameters for the particular drive data set (DDS).
Value:
0:
No
1:
Yes
Note:
If value = 0:
The automatic calculation (p0340, p0578) also overwrites the parameters of the inhibit list (p0571).
If value = 1:
The automatic calculation (p0340, p0578) does not overwrite the parameters of the inhibit list (p0571).
p0571[0...49]
Inhibit list motor/closed-loop control parameter calculation / Inhib list calc
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Applications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2142
0
p0572[0...n]
Activate/deactivate inhibit list / Inh_list act/deact
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Applications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......