4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1824
List Manual (LH2), 07/2016, A5E03263479A
F33163 (N, A)
Encoder 3: Analog sensor position value exceeds limit value
Message value:
%1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Encoder 3
Propagation:
LOCAL
Reaction:
OFF1 (IASC/DCBRK, NONE)
Acknowledge:
PULSE INHIBIT
Cause:
The position value has exceeded the permissible range of -0.5 ... +0.5.
Fault value (r0949, interpret decimal):
1: Position value from the LVDT sensor.
2: Position value from the encoder characteristic.
Remedy:
For fault value = 1:
- check the LVDT ratio (p4678).
- check the reference signal connection at track B.
For fault value = 2:
- check the coefficients of the characteristic (p4663 ... p4666).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A33400 (F, N)
Encoder 3: Alarm threshold zero mark distance error
Message value:
%1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Encoder 3
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The measured zero mark distance does not correspond to the parameterized zero mark distance.
For distance-coded encoders, the zero mark distance is determined from zero marks detected pairs. This means that
if a zero mark is missing, depending on the pair generation, this cannot result in a fault and also has no effect in the
system.
The zero mark distance for the zero mark monitoring is set in p0425 (rotary encoder) or p0424 (linear encoder).
Alarm value (r2124, interpret decimal):
Last measured zero mark distance in increments (4 increments = 1 encoder pulse).
The sign designates the direction of motion when detecting the zero mark distance.
Remedy:
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- check the encoder type (encoder with equidistant zero marks).
- adapt the parameter for the distance between zero marks (p0424, p0425).
- replace the encoder or encoder cable.
Reaction upon F:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A33401 (F, N)
Encoder 3: Alarm threshold zero mark failed
Message value:
%1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Encoder 3
Propagation:
LOCAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 1.5 x parameterized zero mark distance was exceeded.
The zero mark distance for the zero mark monitoring is set in p0425 (rotary encoder) or p0424 (linear encoder).
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...