SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
757
2 Parameters
2.2 List of parameters
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase V (p1829).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1829
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase W (p1830).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1830
Description:
Displays the circulating current of phase U as peak value.
Description:
Displays the circulating current of phase V as peak value.
Description:
Displays the circulating current of phase W as peak value.
p7042[0...n]
Par_circuit correction valve lockout time phase V / Comp t_lockout V
VECTOR_G (Parallel)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-1000000.00 [µs]
1000000.00 [µs]
0.00 [µs]
p7044[0...n]
Par_circuit correction valve lockout time phase W / Comp t_lockout W
VECTOR_G (Parallel)
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-1000000.00 [µs]
1000000.00 [µs]
0.00 [µs]
r7050[0...n]
Par_circuit circulating current phase U / Circ_I_phase U
VECTOR_G (Parallel)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
6_5
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [A]
- [A]
- [A]
r7051[0...n]
Par_circuit circulating current phase V / Circ_I_phase V
VECTOR_G (Parallel)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
6_5
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [A]
- [A]
- [A]
r7052[0...n]
Par_circuit circulating current phase W / Circ_I_phase W
VECTOR_G (Parallel)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
6_5
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [A]
- [A]
- [A]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......