3
F
unction
d
iag
ram
s
3.18
Te
chno
log
y contr
o
ller
SIN
A
MIC
S
G130
/G15
0
12
82
List
Manual (L
H2)
, 07
/2016
, A5E032634
79A
F
ig.
3
-163
79
58 – Close
d-loo
p co
ntro
l (r0
108
.1
6
=
1)
- 7958 -
Function diagram
8
7
6
5
4
3
2
1
fp_7958_51_eng.vsd
DO: SERVO, VECTOR, VECTOR3P, VECTORM2C, VECTORMV
SINAMICS
07.01.15 V04.08.00
Technology controller - Closed-loop control (r0108.16 = 1)
<1>
P, I and D components can be disabled by entering a zero.
<2>
Behavior can be changed via p2252.
<3>
I component stop, only when r2273 and r2294 in same direction.
<4>
Not for VECTOR3P and VECTORMV.
<101> The pre-assignment of the sampling time in p0115[6] is 4000.00 μs.
Tec_ctr t_RU/RD
0.00...100.00 [s]
p2293 (1.00)
Technology controller de-activated
r2349.0
(0)
Tec_ctrl enable
p2200[C]
1
<1>
<1>
<101>
r2294
Tec_ctrl outp_sig
Tec_ctrl setp 1
(0)
p2253[C]
Tec_ctrl set1 scal
0.00...100.00 [%]
p2255 (100.00)
Tec_ctrl t_ramp-up
0.00...650.00 [s]
p2257 (1.00)
Tec_ctrl t_ramp-dn
0.00...650.00 [s]
p2258 (1.00)
r2260
Tec_ctr set aftRFG
Tec_ctrl set T
0.00...60.00 s
p2261 (0.00)
r2262
Tec_ctr set aftFlt
Tec_ctrl setp 2
(0)
p2254[C]
Tec_ctrl set2 scal
0.00...100.00 [%]
p2256 (100.00)
Tec_ctrl act T
0.000...60.000 [s]
p2265 (0.000)
Tec_ctrl act val
(0)
p2264[C]
r2266
Tec_ctr act aftFlt
r2273
Tec_ctrl sys dev
d
dt
Tec_ctrl T diff
0.000...60.000 [s]
p2274 (0.000)
Tec_ctrl max_lim
-200.00...200.00 [%]
p2291 (100.00)
Tec_ctrl Kp
0.000...1000.000
p2280 (1.000)
<1>
Tec_ctrl Tn
0.000...60.000 [s]
p2285 (0.000)
+
+
Tec_ctr prectr_sig
(0)
p2289[C]
Technology controller limited
r2349.1
(2295)
p2296[C]
Tec_ctrl outp scal
-100.00...100.00 %
p2295 (100.00)
p2295
p2291
Tec_ctrl max_lim
(2291)
p2297[C]
p2292
Tec_ctrl min_lim
(2292)
p2298[C]
r2273
Tec_ctrl sys dev
p2263 = 1
p2263 = 0
Tec_ctrl min_lim
-200.00...200.00 [%]
p2292 (0.00)
p0115[6] (Drive Object)
Tec_reg config
RU/RD t ind sign
p2252.0
p2252.1
p2252.2
p2252.2
Tec_ctrl gain act
0.00...500.00 [%]
p2269 (100.00)
Tec_ctrl act inv
0...1
p2271 (0)
Tec_ctr ActVal fct
0...3
p2270 (0)
r2272
Tech_ctrl act scal
Tec_ctrl type
0 = D component in actual
value signal
1 = D component in fault signal
p2263(0)
-1
<2>
<2>
<2>
<2>
Tec_ctrl lim offs
(0)
p2299[C]
(r0056.13)
Tec_ctr integ hold
p2286[C]
<3>
<4>
<4>
<4>
<4>
0
1
Tec_ctrl u_lim act
-10000.00...10000.00 [%]
p2267 (200.00)
F07426
"Technology controller actual value limited"
<4>
<4>
<4>
0
1
0
p2252.3
0
Tec_ctrl i_lim act
-10000.00...10000.00 [%]
p2268 (-200.00)
1
0
<4>
+
+
+
+
+
+
+
+
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......