Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Code numbers can only be selected for motor types that correspond to the motor type selected in p0300. For 1PH2,
1PH4, 1PH7, 1PM4, 1PM6, 1FT6 motors, code numbers are also possible, whose fourth decimal position is greater
by a value of 1 or 2 than the matching motor type in p0300. For 1FE1 motors, the third decimal position can be higher
by a value of 1.
Refer to: p0300
Note:
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
For a motor with DRIVE-CLiQ, p0301 cannot be changed. In this case, p0301 is automatically written to the code
number of the motor parameter read in (r0302) if p0300 is set to 10000.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
Description:
Displays the motor code number from the saved motor data from a motor with DRIVE-CLiQ.
Note:
Drive commissioning can only be exited if the code number that was downloaded (r0302) matches the stored code
number (p0301). If the numbers differ, then the motor data set should be re-loaded using p0300 = 10000.
The motor data are always expected from the first encoder that is assigned to the drive data sets (refer to p0187 =
encoder 1) data set number.
The value is not updated cyclically but only on specific events (e.g. update DRIVE-CLiQ device).
r0302 = 0: No motor with DRIVE-CLiQ found
Description:
Displays the status word of the automatic motor parameter sensing of a motor with DRIVE-CLiQ.
Motor parameter sensing takes place in the following events if the SMI is connected to the Motor Module and the
encoder is activated (p0145):
- Warm restart
- downloading projects.
- POWER ON (switch-off/switch-on).
- where p0300 = 10000, 10001.
p0301[0...n]
Motor code number selection / Mot code No. sel
VECTOR_G
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
SESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
r0302[0...n]
Motor code number of motor with DRIVE-CLiQ / Mot code mot w/ DQ
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r0303[0...n]
Motor with DRIVE-CLiQ status word / Motor w DQ ZSW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......