2 Parameters
2.2 List of parameters
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
Description:
Sets the U/f control mode of the drive.
Value:
0:
U/f control with linear characteristic
1:
U/f control with linear characteristic and FCC
2:
U/f control with parabolic characteristic
3:
U/f control with parameterizable characteristic
4:
U/f control with linear characteristic and ECO
5:
U/f control for drives requiring a precise freq. (e.g. textiles)
6:
U/f control for drives requiring a precise frequency and FCC
7:
U/f control for a parabolic characteristic and ECO
15:
Operation with braking resistor
19:
U/f control with independent voltage setpoint
Recommendation:
The use of the vector control operating modes is recommended for synchronous motors.
Dependency:
If you are working with reduced supply voltages (p0212.0 = 1), only U/f control with independent voltage setpoint
(p1300 = 19) can be set as the operating mode.
p1300 = 15 (operation with braking resistor), can only be activated or deactivated in quick commissioning (p0010 =
1). This operating mode is only possible for chassis power units (DC/AC Motor Module).
Notice:
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for
the ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note:
The closed-loop torque control can only be changed over in operation (p1300 = 20, 21) by selecting the closed-loop
speed control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is
displayed in r1407, bit 2 and bit 3.
For motors, type p0300 = 14, operation with U/f control is only recommended for diagnostic purposes.
Description:
Sets the open and closed-loop control mode of a drive.
Value:
0:
U/f control with linear characteristic
1:
U/f control with linear characteristic and FCC
2:
U/f control with parabolic characteristic
3:
U/f control with parameterizable characteristic
r1298
CO: Vdc controller output (U/f) / Vdc_ctrl output
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6320
P-Group:
Functions
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
VECTOR_G
Can be changed:
C2(1), T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
6300, 6301,
8012
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 19
0
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
VECTOR_G (n/M)
Can be changed:
C2(1), T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
6300, 6301,
8012
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 23
20
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......