2 Parameters
2.2 List of parameters
SINAMICS G130/G150
120
List Manual (LH2), 07/2016, A5E03263479A
Warning:
For p0247.5 = 1 (only for induction motors):
If the Voltage Sensing Module (VSM) is connected to the line voltage, then the line frequency is interpreted as speed.
In this case, the flying restart function cannot be used together with VSM and the bit should be set to 0.
If only one VSM is connected at the Motor Module, line synchronization must be deactivated (p3800 = 0), in order to
be able to use flying restart together with VSM. If two VSMs are connected, the second VSM is used for flying restart.
Note:
The functions are only available if a Voltage Sensing Module (VSM) is assigned to the Motor Module (p0150, p0151).
Description:
Sets the cooling type for booksize compact power units.
This therefore defines whether for these power units, the internal air cooling is shut down and instead, the "Cold-
Plate" cooling type is used.
Value:
0:
Air cooling int
1:
Cold-Plate
Note:
For booksize compact power units, in the Article number there is a 4 at the 5th position.
The parameter is irrelevant for all other power unit types.
Description:
Displays the power unit fan operating hours.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency:
Refer to: p0252
Refer to: A30042
Note:
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
Description:
Sets the maximum operating time of the power unit fan.
The prealarm (warning) is output 500 hours before this set value.
The monitoring is deactivated with p0252 = 0.
Dependency:
Refer to: p0251
Refer to: A30042
p0249
Power unit cooling type / PU cool type
VECTOR_G
Can be changed:
C2(1, 2)
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p0251[0...n]
Operating hours counter power unit fan / PU fan t_oper
VECTOR_G, B_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
PDS, p0120
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
4294967295 [h]
0 [h]
p0252
Maximum operating time power unit fan / PU fan t_oper max
VECTOR_G, B_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [h]
100000 [h]
40000 [h]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......