2 Parameters
2.2 List of parameters
SINAMICS G130/G150
140
List Manual (LH2), 07/2016, A5E03263479A
Description:
Displays the rated motor torque.
Dependency:
IEC drives (p0100 = 0): unit Nm
NEMA drives (p0100 = 1): unit lbf ft
Note:
For induction and reluctance motors, r0333 is calculated from p0307 and p0311.
For synchronous motors, r0333 is calculated from p0305, p0316, p0327 and p0328. The result can deviate from the
input in p0312. If p0316 = 0, then r0333 = p0312 is displayed.
In the case of multi-motor operation r0333 is increased by the factor p0306 compared to the rated torque of an
individual motor.
Description:
Displays the torque constant of the synchronous motor used.
Dependency:
IEC drives (p0100 = 0): unit Nm / A
NEMA drives (p0100 = 1): unit lbf ft / A
Refer to: p0316
Note:
This parameter is not used for induction motors (p0300 = 1xx).
For synchronous motors, parameter r0334 = p0316 is displayed. For p0316 = 0, r0334 is calculated from p0305 and
p0312 or p0305, p0307, and p0311.
Description:
Sets the motor cooling system used.
Value:
0:
Natural ventilation
1:
Forced cooling
2:
Liquid cooling
4:
Natural ventilation and internal fan
5:
Forced cooling and internal fan
6:
Liquid cooling and internal fan
128:
No fan
Dependency:
For 1LA5 and 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter influences the thermal 3-mass motor model.
1LA1 and 1LA8 motors are characterized by the fact that they have an internal rotor fan. This "internal cooling" lies
within the motor frame and is not visible. Air is not directly exchanged with the motor ambient air.
r0333[0...n]
Rated motor torque / Mot M_rated
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
7_4
Unit selection:
p0100
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r0334[0...n]
Actual motor-torque constant / Mot kT act
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
28_1
Unit selection:
p0100
Not for motor type:
ASM, SESM, REL,
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [Nm/A]
- [Nm/A]
- [Nm/A]
p0335[0...n]
Motor cooling type / Mot cool type
VECTOR_G
Can be changed:
C2(1, 3), T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 128
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......