SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
579
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the status word of the technology controller.
Description:
Sets the signal source for the selection of the "Switch-in motor" function.
When the function is selected, monitoring of the switches is deactivated with the "bypass" function. This means that
the power unit can be connected to other motors via an external control without switch monitoring responding.
Description:
Display and connector output for the reference quantity for speed and frequency (p2000).
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit rpm.
The following applies:
Reference frequency (in Hz) = reference speed (in rpm) / 60
r2349.0...13
CO/BO: Technology controller status word / Tec_ctrl ZSW
VECTOR_G
(Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Technology controller deactivated
Yes
No
-
01
Technology controller limited
Yes
No
-
02
Technology controller motorized
potentiometer limited max
Yes
No
-
03
Technology controller motorized
potentiometer limited min
Yes
No
-
04
Technology controller speed setpoint total in
setpoint channel
Yes
No
-
05
Technology controller RFG bypassed in the
setpoint channel
Yes
No
-
06
Technology controller starting value at the
current limit
No
Yes
-
08
Technology controller actual value at the
minimum
Yes
No
-
09
Technology controller actual value at the
maximum
Yes
No
-
10
Technology controller output at the
minimum
Yes
No
-
11
Technology controller output at the
maximum
Yes
No
-
12
Fault response active
Yes
No
-
13
Technology controller limiting enable
Yes
No
-
p2369
BI: Closed-loop cascade control, control word / Csc_ctrl STW
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
r2700
CO: Reference speed/reference frequency / n_ref/f_ref
VECTOR_G, ENC
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......