2 Parameters
2.2 List of parameters
SINAMICS G130/G150
966
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the PROFIsafe telegram number for the Control Unit.
Value:
0:
No PROFIsafe telegram selected
30:
PROFIsafe standard telegram 30, PZD-1/1
31:
PROFIsafe standard telegram 31, PZD-2/2
900:
PROFIsafe SIEMENS telegram 900, PZD-2/2
901:
PROFIsafe SIEMENS telegram 901, PZD-3/5
902:
PROFIsafe SIEMENS telegram 902, PZD-3/6
998:
Compatibility mode (as for firmware version < 4.5)
Dependency:
Refer to: p9811, p60022
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
Description:
Sets the stop response when PROFIsafe communication fails.
Value:
0:
STOP A
1:
STOP B
Dependency:
Refer to: p9812
Note:
For the set stop response STOP B, in order that the OFF3 ramp is actually maintained, when just using Safety Basic
functions, the following must be carefully observed:
- the transition time STOP F to STOP A (p9658, p9858) must be set longer or equal to the SS1 delay time (p9652,
p9852).
- if a higher-level control responds to a drive fault by withdrawing the controller enable signals, for faults F01611 and
F30611, the message type must be changed to alarm (p2118, p2119).
Description:
Sets the signal source for the following functions on the Control Unit:
STO: Safe Torque Off / SH: Safe standstill
SBC: Safe Brake Control
SS1: Safe Stop 1 (time monitored)
Dependency:
Refer to: p9601
p9611
SI PROFIsafe telegram selection (Control Unit) / SI Ps telegram CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 998
998
p9612
SI PROFIsafe failure response (Control Unit) / SI Ps fail CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p9620[0...7]
BI: SI signal source for STO (SH)/SBC/SS1 (Control Unit) / SI S_srcSTO/SS1 CU
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
2810
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......