SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1055
2 Parameters
2.2 List of parameters
Description:
Activates the readback input for the safety digital outputs (F-DO)
The test mode for the particular safety digital output is set in p10047.
Dependency:
Refer to: p10047
Note:
F-DO: Failsafe Digital Output
Description:
Sets the test stop mode for the particular safety digital output (F-DO)
Index 0: F-DO 0
Index 1: F-DO 1
Index 2: F-DO 2
Index 3: F-DO 3
Value:
1:
Test mode 1 evaluation of int. diagnostic signal (passive load)
2:
Test mode 2 read back F-DO in DI (relay circuit)
3:
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Note:
If value = 1:
When this test mode is being used, and excessive resistance of the load between DO+ and DO- can lead to
problems during the test stop. It is therefore important to make sure that the load resistance at an individual F-DO
does not exceed 10 kOhm.
Description:
Configures the test stop for F-DI and F-DO of the TM54F.
If the automatic test stop is activated, then the test stop can still be started using binector input p10007.
Note:
The automatic test stop is started after power up, partial power up or a warm restart.
Value:
0:
Manual test stop via BICO p10007
1:
Automatic test stop
p10046
SI TM54F F-DO feedback signal input activation / SI F-DO FS act
TM54F_MA,
TM54F_SL
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
2892
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Read back F-DO 0
Test active
No test
-
01
Read back F-DO 1
Test active
No test
-
02
Read back F-DO 2
Test active
No test
-
03
Read back F-DO 3
Test active
No test
-
p10047[0...3]
SI TM54F F-DO test stop mode / SI F-DO test mode
TM54F_MA,
TM54F_SL
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 3
2
p10048
SI TM54F F-DI F-DO test stop configuration / SI teststop config
TM54F_MA
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......