2 Parameters
2.2 List of parameters
SINAMICS G130/G150
362
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the cause that should initiate the bypass.
Note:
The parameter only has an effect for a non-synchronized bypass.
p1267.0 = 1:
The bypass is initiated by setting a binary signal. When the command is reset, after the debypass delay time (p1263)
has expired, operation at the power unit is re-selected.
p1267.1 = 1:
When the speed threshold entered in p1265 is reached, the bypass is switched in. The system only switches back
when the speed setpoint again falls below the threshold value.
Description:
Sets the signal source for the feedback signal "synchronization completed" for the bypass function.
Dependency:
Refer to: r3819
Description:
Sets the signal source for the feedback signal of the bypass switch.
Index:
[0] = Switch motor/drive
[1] = Switch motor/line supply
Note:
In the case of switches without a feedback signal, interconnect the corresponding control bit as the signal source:
BI: p1269[0] = r1261.0
BI: p1269[1] = r1261.1
p1267
Bypass changeover source configuration / Chngov_src config
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Bypass via signal (BI: p1266)
Yes
No
-
01
Bypass via reaching the speed threshold
Yes
No
-
p1268
BI: Bypass feedback synchronization completed / FS sync compl
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
3819.2
p1269[0...1]
BI: Bypass switch feedback signal / Bypass FS
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......