SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
265
2 Parameters
2.2 List of parameters
Description:
Sets the setpoint for the input signals in the digital input simulation mode.
Dependency:
The simulation of a digital input is selected using p0795.
Refer to: p0795
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the sampling time for the inputs and outputs of the Control Unit.
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Not available - analog inputs (AI)
[2] = Not available - analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
Refer to: p0009
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
p0796
CU digital inputs simulation mode setpoint / CU DI simul setp
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
2020, 2030,
2031, 2100, 2119, 2120, 2130,
2131, 2132, 2133
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X122.1/X121.1)
High
Low
-
01
DI 1 (X122.2/X121.2)
High
Low
-
02
DI 2 (X122.3/X121.3)
High
Low
-
03
DI 3 (X122.4/X121.4)
High
Low
-
04
DI 4 (X132.1 / -)
High
Low
-
05
DI 5 (X132.2 / -)
High
Low
-
06
DI 6 (X132.3 / -)
High
Low
-
07
DI 7 (X132.4 / -)
High
Low
-
08
DI/DO 8 (X122.9/X121.7)
High
Low
-
09
DI/DO 9 (X122.10/X121.8)
High
Low
-
10
DI/DO 10 (X122.12/X121.10)
High
Low
-
11
DI/DO 11 (X122.13/X121.11)
High
Low
-
12
DI/DO 12 (X132.9/X131.1)
High
Low
-
13
DI/DO 13 (X132.10/X131.2)
High
Low
-
14
DI/DO 14 (X132.12/X131.4)
High
Low
-
15
DI/DO 15 (X132.13/X131.5)
High
Low
-
16
DI 16 (X122.5/X120.3)
High
Low
-
17
DI 17 (X122.6/X120.4)
High
Low
-
20
DI 20 (X132.5/X120.9)
High
Low
-
21
DI 21 (X132.6/X120.10)
High
Low
-
p0799[0...2]
CU inputs/outputs sampling time / CU I/O t_sampl
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2020, 2030,
2031
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
4000.00 [µs]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......