SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
705
2 Parameters
2.2 List of parameters
Description:
Sets the bit mask for the bit mask trigger.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 6 or p4710 = 8.
Description:
Sets the trigger condition for bit mask trigger.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 6.
Description:
Sets the number of averaging operations for the measuring function.
Description:
Sets the number of stabilizing periods for the measuring function.
Description:
Displays the trigger index in the trace buffer. The trigger event occurred at this point.
Index:
[0] = Trace 0
[1] = Trace 1
p4715[0...1]
Trace bit mask trigger, bit mask / Trace trig mask
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0 4294967295
0
p4716[0...1]
Trace bit mask trigger trigger condition / Trace Trig_cond
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0 4294967295
0
p4717
Measuring function number of averaging operations / Meas fct avg qty
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0 255
0
p4718
Measuring function number of stabilizing periods / MeasFct StabPerQty
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0 255
0
r4719[0...1]
Trace trigger index / Trace Trig_index
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......