2 Parameters
2.2 List of parameters
SINAMICS G130/G150
630
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for the message "pre-alarm I*t shutdown" of the Braking Module.
BI: p3865[0...7] = 1 signal --> no pre-alarm, I*t shutdown
BI: p3865[0...7] = 0 signal --> pre-alarm I*t shutdown (A06901)
Dependency:
Refer to: A06901
Note:
For the Braking Module, this message is output via the following terminal:
- X21.4 for the "Booksize" format
This function is not supported for the "chassis" format.
Description:
Sets the signal source for the "Fault" message of the Braking Module.
BI: p3866[0...7] = 1 signal --> No fault
BI: p3866[0...7] = 0 signal --> fault (A06900)
For a 0 signal, an acknowledgment via BO: r3861 is automatically carried out at certain time intervals.
Dependency:
Refer to: A06900
Note:
For the Braking Module, this message is output via the following terminal:
- X21.4 for the "Booksize" format
- X21.5 for the "Chassis" format
Description:
Sets the signal source to activate the essential service mode (ESM) via digital input.
Using this function, when required the motor can be operated for as long as possible (e.g. to extract smoke).
BI: p3880 = 1 signal:
The essential service mode is activated.
BI: p3880 = 0 signal:
The essential service mode is deactivated.
Dependency:
The function can only be activated for SINAMICS G130/G150/S150.
Refer to: p3881, p3882, p3883, p3886, r3887, p3888, r3889
Warning:
When activating the essential service mode (BI: p3880 = 1 signal), the motor immediately runs according to the
selected setpoint source. When the essential service mode is activated, the motor cannot be stopped using the OFF
commands.
Note:
ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 17, 20, 21
p3865[0...7]
BI: Braking Module pre-alarm I*t shutdown / BM I*t shutdown
B_INF (Brk Mod ext)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9951
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p3866[0...7]
BI: Braking Module fault / BM fault
B_INF (Brk Mod ext)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9951
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p3880
BI: ESM activation signal source / ESM act s s
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
7033
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......