SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
383
2 Parameters
2.2 List of parameters
Description:
Sets the braking resistor for the braking chopper.
Dependency:
Select operation with braking resistor: p1300 = 15
Refer to: p1362, r1363, p1364
Refer to: A06921, F06922
Description:
Sets the activation threshold for the brake chopper.
The hysteresis defines the range of the output voltage from zero up to the maximum voltage.
Index:
[0] = Braking chopper threshold value
[1] = Braking chopper hysteresis
Dependency:
Select operation with braking resistor: p1300 = 15
Refer to: p1360, r1363, p1364
Refer to: A06921, F06922
Description:
Displays the actual power unit output voltage (Motor Module) in braking chopper operation.
Dependency:
Select operation with braking resistor: p1300 = 15
Refer to: p1360, p1362, p1364
Refer to: A06921, F06922
Description:
Sets the percentage value for the asymmetry detection for the braking chopper.
The ripple of the absolute current r0068 is monitored.
The reference value is the average value of the absolute current.
The minimum monitoring value is 10 % of the power unit rated current.
p1360
Braking chopper braking resistor cold / Br_chop R cold
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [ohm]
10.000 [ohm]
0.000 [ohm]
p1362[0...1]
Braking chopper activation threshold / Br_chop thresh
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [V]
1158 [V]
[0] 0 [V]
[1] 60 [V]
r1363
CO: Braking chopper output voltage / Br_chop U_output
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
5_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
p1364
Braking chopper resistor asymmetry / Br_chop R asym
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
V/f open-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
100.00 [%]
25.00 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......