2 Parameters
2.2 List of parameters
SINAMICS G130/G150
394
List Manual (LH2), 07/2016, A5E03263479A
Description:
Display and connector output for the system deviation of the I component of the speed controller.
When the reference model is inactive (p1433 = 0 Hz), this parameter corresponds to the system deviation of the
complete PI controller (r1454 = r0064).
Description:
Sets the source for the adaptation signal to additionally adapt the P gain of the speed controller.
Dependency:
Refer to: p1456, p1457, p1458, p1459
Description:
Sets the lower starting point of the adaptation range for the additional adaptation of the P gain of the speed controller.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Refer to: p1455, p1457, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
Description:
Sets the upper starting point of the adaptation range for the additional adaptation of the P gain of the speed
controller.
The values are in % and refer to the set source of the adaptation signal.
Dependency:
Refer to: p1455, p1456, p1458, p1459
Note:
If the upper transition point p1457 of the speed controller adaptation is set to lower values than the lower transition
p1456, then the controller gain below p1457 is adapted with p1459 and above p1456, with p1458.
r1454
CO: Speed controller system deviation I component / n_ctrl sys dev Tn
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6040
P-Group:
Closed-loop control
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1455[0...n]
CI: Speed controller P gain adaptation signal / n_ctr adapt_sig Kp
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p1456[0...n]
Speed controller P gain adaptation lower starting point / n_ctrl AdaptKpLow
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
400.00 [%]
0.00 [%]
p1457[0...n]
Speed controller P gain adaptation upper starting point / n_ctrl AdaptKp up
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
400.00 [%]
0.00 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......