2 Parameters
2.2 List of parameters
SINAMICS G130/G150
576
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the proportional gain (P component) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2280 = 0: The proportional gain is disabled.
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2285 = 0: The integral time is disabled.
Description:
Sets the signal source to hold the integrator for the technology controller.
Description:
Sets the signal source for the pre-control signal of the technology controller.
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2280
Technology controller proportional gain / Tec_ctrl Kp
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 1000.000
1.000
p2285
Technology controller integral time / Tec_ctrl Tn
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
p2286[0...n]
BI: Hold technology controller integrator / Tec_ctr integ hold
VECTOR_G
(Tech_ctrl)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctr prectr_sig
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......