SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
115
2 Parameters
2.2 List of parameters
Notice:
When connected to 3-ph. 230 V AC (only booksize units) the following must be observed:
- the undervoltage and overvoltage limits change (r0296, r0297).
- when using the internal braking chopper of Basic Line Modules (20 or 40 kW) the threshold when the braking
chopper becomes active is reduced to 385 V. When using an external braking chopper, it must be ensured that a
suitable activation threshold is used.
- all of the components connected to this DC link must also be adapted to the low line supply voltage. It is especially
important that the rated DC voltage of all of the drives connected to this DC link is set with p0210 (e.g.
p0210(SERVO) = 1.35 x p0210(B_INF) = 310 V).
- it is not possible to use a Control Supply Module (CSM) to generate a 24 V supply from the DC link, as the minimum
continuous DC link voltage should not be below 430 V.
Note:
The supply voltage range depends on the voltage class of the power unit.
400 V chassis units: 380 V <= p0210 <= 480 V
690 V chassis units: 500 V <= p0210 <= 690 V
400 V booksize units can also be connected to 3-ph. 230 V AC:
400 V booksize units: 180 V <= p0210 <= 480 V
A reduced supply voltage up to 70 V is possible if p0212.0 = 1 has been set.
Description:
Sets the power unit configuration.
Dependency:
For bit 00:
Reduced supply voltages are only possible for booksize and chassis power units (DC/AC).
Bit 0 = 1 can only be set if r0192.22 = 1.
For bit 01 = 1:
The external precharging setting only affects the DC/AC power units.
For bit 03 = 1:
The automatic adaptation (reduction) of the Vdc max limit is deactivated (only for chassis power units). Bit 3 only has
an effect, if bit 0 is simultaneously set.
Refer to: r0192, p0210
Caution:
For bit 00:
Working with reduced input voltages deactivates undervoltage detection.
For bit 03:
If the automatic setting of the Vdc max limit is deactivated, then all of the components connected to the DC link must
be suitable for the maximum DC link voltage of the power unit (e.g. 820 V for 400 V units).
Note:
For bit 00 = 0:
It is not possible to reduce the supply voltage in p0210.
For bit 00 = 1:
With this setting the supply voltage in p0210 can be reduced to 100 V.
Booksize PU: only for operating mode p1300 = 19
Chassis PU: only for operating mode p1300 > 19 and closed-loop DC voltage control
For bit 01 = 0:
There is no external precharging of the DC/AC Motor Modules. The precharging monitoring is bypassed.
For bit 01 = 1:
There is external precharging of the DC/AC Motor Modules. The precharging monitoring is calculated.
For bit 03 = 0:
The DC link voltage limit is calculated from p0210.
p0212
Power unit configuration / PU config
VECTOR_G
Can be changed:
C2(2)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-
-
0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Drive unit line supply voltage reduced
Yes
No
-
01
External precharging present
Yes
No
-
03
Automatically adapt Vdc_max limit
No
Yes
-
05
Contactor display inputs/outputs status
Yes
No
9814
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......