2 Parameters
2.2 List of parameters
SINAMICS G130/G150
272
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the configuration for the motor and encoder changeover.
Note:
For bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate motor
data sets.
For bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
For motor changeover to running motor:
The "flying restart" function should also be activated (p1200) when changing over to a motor that is already running.
Description:
Display and BICO output for the status word of the data set switchover.
Note:
This parameter is only supplied with up-to-date values if data set changeover has been selected or is running.
For bit 00:
The signal is only influenced when a motor changeover is set via p0827 (unequal bit numbers).
For bit 01:
The signal is only influenced when an encoder changeover is set via p0187, p0188, or p0189.
For bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
For bit 04:
A data set changeover is only carried out when the armature short circuit is not activated.
p0833
Data set changeover configuration / DS_chng config
VECTOR_G
Can be changed:
C2(15)
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8575
P-Group:
Data sets
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0010
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Contactor changeover from the
application/drive
Application
Drive
-
01
Pulse suppression by application/drive
Application
Drive
-
02
Suppress drive parking for EDS changeover Yes
No
-
r0835.0...11
CO/BO: Data set changeover status word / Data set sw ZSW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8575
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor changeover active
Yes
No
8575
01
Encoder changeover active
Yes
No
-
02
Internal parameter calculation active
Yes
No
-
04
Armature short circuit active
Yes
No
-
05
Identification running
Yes
No
-
06
Friction characteristic plot running
Yes
No
-
07
Rotating measurement running
Yes
No
-
08
Motor data identification running
Yes
No
-
10
Wait for pulse suppression
Yes
No
-
11
Wait for motor changeover feedback signal
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......