4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1426
List Manual (LH2), 07/2016, A5E03263479A
Example 2:
BICO output with voltage normalized unit in drive object 1 (DO1), BICO input with voltage normalized unit in drive
object 2 (DO2). The reference values for voltage (p2001) of the two drive objects have different values. This means
that the factor p2001(DO1)/p2001(DO2) is calculated between the BICO output and the BICO input.
p2001: contains the reference value for voltage, drive objects 1, 2
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A01514 (F)
BICO: Error when writing during a reconnect
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Propagation:
BICO
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. while booting or downloading - but can also occur in normal operation) a
parameter was not able to be written to.
Example:
When writing to BICO input with double word format (DWORD), in the second index, the memory areas overlap (e.g.
p8861). The parameter is then reset to the factory setting.
Alarm value (r2124, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
F01515 (A)
BICO: Writing to parameter not permitted as the master control is active
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing the number of CDS or when copying from CDS, the master control is active.
Remedy:
If required, return the master control and repeat the operation.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A01590 (F)
Drive: Motor maintenance interval expired
Message value:
Fault cause: %1 bin
Message class:
General drive fault (19)
Drive object:
All objects
Component:
Motor
Propagation:
GLOBAL
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected service/maintenance interval for this motor was reached.
Alarm value (r2124, interpret decimal):
Motor data set number.
See also: p0650 (Actual motor operating hours), p0651 (Motor operating hours maintenance interval)
Remedy:
carry out service/maintenance and reset the service/maintenance interval (p0651).
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......