4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1682
List Manual (LH2), 07/2016, A5E03263479A
- Using STARTER, activate the safety parameters for the drive involved (change settings, copy parameters, activate
settings).
- switch off and switch on the drive unit and DRIVE-CLiQ components. If A30650 is still present, repeat the download.
- replace the memory card or Control Unit.
For fault value = 2000:
- check the safety parameters on monitoring channel 2 and adapt the reference checksum (p9899).
For fault value = 2003, 2005:
- carry out an acceptance test and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in
the following literature:
SINAMICS S120 Function Manual Safety Integrated
For fault value = 3003:
- carry out the function checks for the modified hardware and generate an acceptance report.
The procedure when carrying out an acceptance test as well as an example of the acceptance report are provided in
the following literature:
SINAMICS S120 Function Manual Safety Integrated
For fault value = 9999:
- carry out diagnostics for the other safety-related fault that is present.
Note:
MM: Motor Module
SI: Safety Integrated
See also: p9799 (SI reference checksum SI parameters (Control Unit)), p9899 (SI reference checksum SI
parameters (Motor Module))
F30651
SI P2: Synchronization with Control Unit unsuccessful
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function requires synchronization of the safety time slices in both monitoring
channels. This synchronization routine was unsuccessful.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade the Motor Module/Hydraulic Module software.
- upgrade the Control Unit software.
Note:
MM: Motor Module
SI: Safety Integrated
F30652
SI P2: Illegal monitoring clock cycle
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Propagation:
LOCAL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The Safety Integrated monitoring clock cycle cannot be maintained due to the communication conditions requested in
the system.
Note:
This fault results in a STOP A that cannot be acknowledged.
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......