2 Parameters
2.2 List of parameters
SINAMICS G130/G150
902
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the node identifier of the Sensor Module that is used by the Motor Module/Hydraulic Module for the motion
monitoring functions.
Dependency:
Refer to: r9881
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Description:
Sets the bit number for the safe most significant bit (MSB) of the Gx_XIST1 coarse position.
The encoder that is used for the safe motion monitoring functions on the Motor Module/Hydraulic Module must be
parameterized in this parameter.
Dependency:
Refer to: p0415, r0475, p9529
Note:
MSB: Most Significant Bit
Description:
Sets the tolerance for the function "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9530
Refer to: C01707
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SOS: Safe Operating Stop
Description:
Sets the tolerance for the function "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9530
Refer to: C01707
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SOS: Safe Operating Stop
p9328[0...11]
SI Motion Sensor Module Node Identifier (Motor Module) / SI Mtn SM Ident MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
00FF hex
0000 hex
p9329
SI Motion Gx_XIST1 coarse pos safe most significant bit (MM) / Gx_XIST1 MSB MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 31
14
p9330
SI Motion standstill tolerance (Motor Module) / SI Mtn SOS Tol MM
VECTOR_G
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [mm]
100.000 [mm]
1.000 [mm]
p9330
SI Motion standstill tolerance (Motor Module) / SI Mtn SOS Tol MM
VECTOR_G (Safety
rot)
Can be changed:
C2(95)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [°]
100.000 [°]
1.000 [°]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......