2 Parameters
2.2 List of parameters
SINAMICS G130/G150
60
List Manual (LH2), 07/2016, A5E03263479A
Bit 17 = 1 (enable signal missing), if:
- the commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
Description:
Displays the actual status for the motor data identification (stationary measurement) and the speed/velocity controller
optimization (rotating measurement).
Value:
0:
No measurement
115:
Measurement q leakage inductance (part 2)
120:
Speed controller optimization (vibration test)
140:
Calculate speed controller setting
150:
Measurement moment of inertia
170:
Measurement magnetizing current and saturation characteristic
190:
Speed encoder test
195:
Measurement q leakage inductance (part 1)
200:
Rotating measurement selected
210:
Pole position identification selected
220:
identification leakage inductance
230:
Identification rotor time constant
240:
Identification stator inductance
250:
Identification stator inductance LQLD
260:
Identification circuit
270:
Identification stator resistance
290:
Identification valve lockout time
300:
Stationary measurement selected
Note:
For r0047 = 300:
This value is also displayed if encoder calibration p1990 is selected.
Description:
Displays the effective Motor Data Set (MDS) and the effective Encoder Data Sets (EDS).
Index:
[0] = Motor Data Set MDS effective
[1] = Encoder 1 Encoder Data Set EDS effective
[2] = Encoder 2 Encoder Data Set EDS effective
[3] = Encoder 3 Encoder Data Set EDS effective
Dependency:
Refer to: p0186, p0187, p0188, p0189, r0838
Note:
Value 99 means the following: No encoder assigned (not configured).
r0047
Motor data identification and speed controller optimization / MotID and n_opt
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 300
-
r0049[0...3]
Motor data set/encoder data set effective / MDS/EDS effective
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
8565
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......