2 Parameters
2.2 List of parameters
SINAMICS G130/G150
606
List Manual (LH2), 07/2016, A5E03263479A
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description:
Displays the internal status of the infeed module.
Value:
0:
Initialization
1:
Fault
2:
No ON command
3:
Offset measurement running
4:
ON delay active
5:
Precharging running
6:
Operation
Description:
Display and BICO output for the status word of the DC link voltage control.
Dependency:
Refer to: A06810
Note:
For bit 01:
DC link voltage control is disabled and enabled with p3513.
For bit 08 = 1:
DC link voltage control is selected using p3513.
Description:
Display and BICO output for the status word of the infeed unit.
Dependency:
Refer to: A06810
Note:
For bit 07:
When the alarm threshold is fallen below, alarm A06810 is output and r3405.7 is set = 1.
The alarm threshold is obtained from the sum of the undervoltage threshold p0296 and offset r0279. As a
consequence, the alarm threshold is only effective for p0279 > 0.
Monitoring only takes place when operational.
The following applies for states r3402 <= 5 and r3402 = 12: r3405.7 = 0.
r3402
Infeed status internal BIC / INF state int
B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
8932
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 6
-
r3405.1...8
CO/BO: Status word DC link control / ZSW Vdc_ctrl
VECTOR_G
(Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Vdc-ctrl active
Yes
No
-
08
Vdc controller selected
Yes
No
-
r3405.7
CO/BO: Infeed status word / Inf ZSW
B_INF
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
DC link undervoltage alarm threshold
undershot
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......