2 Parameters
2.2 List of parameters
SINAMICS G130/G150
404
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for toggling between speed and torque control.
0 signal: Closed-loop speed control
1 signal: Closed-loop torque control
Dependency:
The input connectors to enter the torque are provided using p1511, p1512 and p1513.
Refer to: p1300
Notice:
If the closed-loop torque control is not activated (p1300) and a change is made to closed-loop torque control (p1501),
OFF1 (p0840) does not have its own braking response but pulse suppression when standstill is detected (p1226,
p1227).
Note:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source to freeze the estimated moment of inertia.
0 signal:
Moment of inertia estimator active
1 signal:
Determined moment of inertia frozen.
Dependency:
Refer to: p1300
Note:
Only active when the "moment of inertia estimator" function module is active (r0108.10 = 1) and p1400.18 =1.
For operation with encoder, p1400.23 must also be set to 1.
Description:
Sets the signal source for the torque setpoint for torque control.
Note:
A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the
selection was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
p1501[0...n]
BI: Change over between closed-loop speed/torque control / Changeov n/M_ctrl
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2520, 6020
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1502[0...n]
BI: Freeze moment of inertia estimator / J_estim freeze
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1503[0...n]
CI: Torque setpoint / M_set
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6020, 6060
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......