SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
349
2 Parameters
2.2 List of parameters
Description:
Sets the delay time for pulse suppression.
After OFF1 or OFF3, the pulses are canceled, if at least one of the following conditions is fulfilled:
- the speed actual value falls below the threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the threshold in p1226 and the time started after this in p1227 has expired.
Dependency:
Refer to: p1226, p1227
Notice:
When the motor holding brake is activated, pulse cancellation is additionally delayed by the brake closing time
(p1217).
Description:
Displays the status word for the motor holding brake.
Description:
Sets the signal source to activate the armature short-circuit or DC braking.
Dependency:
Refer to: p1231, p1232, p1233, p1234, p1235, p1236, p1237, r1238, r1239, p1345, p1346
Note:
1 signal: Armature short-circuit/DC braking activated.
0 signal: Armature short-circuit/DC braking deactivated.
p1228
Pulse suppression delay time / Pulse suppr t_del
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2701, 2704
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
299.000 [s]
0.000 [s]
r1229.1...11
CO/BO: Motor holding brake status word / Brake ZSW
VECTOR_G (Ext
brake)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Command open brake (continuous signal)
Yes
No
2711
03
Pulse enable extended brake control
Yes
No
2711
04
Brake does not open
Yes
No
2711
05
Brake does not close
Yes
No
2711
06
Brake threshold exceeded
Yes
No
2707
07
Brake threshold undershot
Yes
No
2704
08
Brake monitoring time expired
Yes
No
2704
09
Pulse enable request missing/n_ctrl
inhibited
Yes
No
2707
10
Brake OR logic operation result
Yes
No
2707
11
Brake AND logic operation result
Yes
No
2707
p1230[0...n]
BI: Armature short-circuit / DC braking activation / ASC/DCBRK act
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
7014, 7016,
7017
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......