SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
619
2 Parameters
2.2 List of parameters
Description:
Sets the frequency limiting of the phase controller output for the line-drive synchronization.
Description:
Displays the correction frequency for the line-drive synchronization.
Description:
Sets the threshold value of the phase synchronism for the line-drive synchronization.
A prerequisite for synchronism is achieved if the phase difference is lower than the threshold value.
Note:
Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
Description:
Display and connector output for the voltage difference between the measured target voltage and output voltage of
the gating unit of the closed-loop control for line-drive synchronization.
Description:
Sets the threshold value of the voltage difference for the line-drive synchronization.
A prerequisite for synchronism is reached if the voltage difference is less than the threshold value.
p3811[0...n]
Sync-line-drive frequency limiting / Sync f_lim
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
1.00 [Hz]
0.20 [Hz]
r3812
CO: Sync-line-drive correction frequency / Sync f_corr
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
3080, 7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
p3813[0...n]
Sync-line-drive phase synchronism threshold value / Sync Ph_sync thrsh
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1.00 [°]
20.00 [°]
2.00 [°]
r3814
CO: Sync-line-drive voltage difference / Sync U_diff
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2001
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
p3815[0...n]
Sync-line-drive voltage difference threshold value / Sync U_diff thresh
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
7020
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
20.00 [%]
10.00 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......