2 Parameters
2.2 List of parameters
Description:
Sets the scaling of the pre-control characteristic for the start of field weakening.
For values above 100 % and for partial load situations, the field weakening starts at higher speeds.
Note:
If the start of field weakening is shifted to lower speeds, then the voltage reserve is increased for partial load
situations.
If the start of field weakening is shifted to higher speeds, the voltage reserve is appropriately reduced so that for fast
load changes, it can be expected that this will have a negative impact on the dynamic performance.
Description:
Displays the pre-control value for the field weakening current.
Description:
Sets the proportional gain for the flux controller.
Note:
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
Description:
Sets the integral time for the flux controller.
Note:
The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1586[0...n]
Field weakening characteristic scaling / Field weak scal
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
80.0 [%]
120.0 [%]
100.0 [%]
r1589
Field-weakening current pre-control value / I_FieldWeak prectr
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6724
P-Group:
Closed-loop control
Unit group:
6_2
Unit selection:
p0505
Not for motor type:
ASM, SESM, REL
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
p1590[0...n]
Flux controller P gain / Flux controller Kp
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6723
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 999999.0
10.0
p1592[0...n]
Flux controller integral time / Flux controller Tn
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6723
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
10000 [ms]
30 [ms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......