SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
397
2 Parameters
2.2 List of parameters
Description:
Sets the upper adaptation speed of the speed controller.
No adaptation is effective above this speed.
For the proportional gain, p1460 x p1461 is effective.
For the integral time, p1462 x p1463 is effective.
Dependency:
The parameter is set by the speed controller optimization. Adaptation to the application should then be subsequently
made.
Refer to: p1460, p1461, p1462, p1463, p1464
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
point p1464, then the controller below p1465 is adapted with p1461 or p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
Description:
Sets the signal source for the scaling of the P gain of the speed controller.
This also makes the effective P gain (including adaptations) scalable.
Description:
Displays the effective P gain of the speed controller.
Dependency:
For p0528 = 1, the speed controller gain is represented without any dimensions. In this case, connector output signal
r1468 is increased by a factor of 100 in order to improve the resolution.
Description:
Displays the effective integral time of the speed controller.
p1465[0...n]
Speed controller adaptation speed upper / n_ctrl n upper
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
210000.00 [rpm]
p1466[0...n]
CI: Speed controller P-gain scaling / n_ctrl Kp scal
VECTOR_G (n/M)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
1
r1468
CO: Speed controller P-gain effective / n_ctr Kp eff
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
6040
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r1469
Speed controller integral time effective / n_ctr Tn eff
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
5040, 5042,
6040
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......