2 Parameters
2.2 List of parameters
Description:
Sets the maximum speed/velocity for the motorized potentiometer.
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description:
Sets the minimum speed/velocity for the motorized potentiometer.
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
switched off.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
p1037[0...n]
Motorized potentiometer maximum speed / MotP n_max
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1038[0...n]
Motorized potentiometer minimum speed / MotP n_min
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1039[0...n]
BI: Motorized potentiometer inversion / MotP inv
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1040[0...n]
Motorized potentiometer starting value / Mop start value
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3020
P-Group:
Setpoints
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......