2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the status word of the essential service mode (ESM).
Note:
ESM: Essential Service Mode
Description:
Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700, p1000 and
p1500 are re-established and all of the dependent motor, open-loop and control-loop control parameters are
calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700, p1000 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick parameterization (only) for BICO and motor parameters
3:
Quick parameterization for motor parameters (only)
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motors p0320, p0352, p0353, p0362 ... p0369, p0391 ... p0393, p0604, p0605, p0626 ... p0628
synchronous motor p0326, p0327, p0352, p0353, p0391 ... p0393, p0604, p0605.
r3889.0...10
CO/BO: ESM status word / ESM ZSW
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
7033
P-Group:
Functions
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Essential service mode (ESM) activated
Yes
No
-
01
Direction of rotation inverted
Yes
No
-
02
Setpoint signal lost
Yes
No
-
07
Setpoint TB30/TM31 analog input
parameterized (p3886)
Yes
No
-
08
Power unit not permissible (permissible
p0201 >= 14000)
Yes
No
-
09
Response OFF1/OFF2 activated
Yes
No
-
10
Automatic restart interrupted (F07320)
Yes
No
-
p3900
Completion of quick commissioning / Compl quick_comm
VECTOR_G
Can be changed:
C2(1)
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......