3
F
unction
d
iag
ram
s
3.6
P
ROFIdrive
SIN
A
MIC
S
G130
/G15
0
11
5
6
List
Manual (L
H2)
, 07
/2016
, A5E032634
79A
F
ig.
3
-50
24
85 – IF
2 receive
tele
gram,
free in
terco
nnection
- 2485 -
Function diagram
8
7
6
5
4
3
2
1
fp_2485_54_eng.vsd
DO: ENC, SERVO, TM41, VECTOR
S120/S150/G130/G150
27.06.13 V04.08.00
PROFIdrive - IF2 receive telegram, free interconnection
PZD receive word 1
PZD receive word 2
r8860[0]
DWORD
r8860[4]
DWORD
r8891.0
r8850[1]
r8891.15
r8890.0
r8850[0]
r8890.15
...
PZD receive word 3
PZD receive word 4
r8860[2]
DWORD
r8893.0
r8850[3]
r8893.15
r8892.0
r8850[2]
r8892.15
...
...
r8860[1]
DWORD
...
r8850[4]
r8860[3]
DWORD
PZD receive word 32
r8850[30]
r8860[30]
DWORD
r8850[31]
(0)
p8899[0]
r8895.0
r8895.15
(0)
p8899[1]
Reference quantities for further interconnection
p200x
<3>
<3>
2 connector-binector converter
<4>
r8894.0
r8894.15
<1> The number of PZD receive words depends on the drive object type.
<2> The connector-binector converter only converts the lower 16 bits irrespective of the input variable.
<3> The following representation applies for words: 4000 hex = 100 % for double words 40000 0000 hex = 100 %.
The reference variables p200x apply for the ongoing interconnection (100 % -> p200x).
The following applies for temperature values: 100 °C -> 100 % = 4000 hex or 40000 0000 hex; 0 °C -> 0 %.
<4> Using the connector-binector converters, the bits can be extracted from two of the PZD receive words 5 to 16 and used as binectors.
<5> Every PZD word can be assigned a word or a double word. Only one of the 2 interconnection parameters r8850 or r8860 can have a value 0 for a PZD word.
<6> When interconnecting a connector output multiple times all the connector inputs must have either Integer or FloatingPoint data type.
p8898[1].0
p8898[1].15
p8898[0].15
p8898[0].0
receive telegram
1
0
1
1
0
1
1
0
1
1
0
1
<4>
Drive object n
Header
Drive object 1
Drive object 2
.
.
.
.
.
.
Drive object m
Trailer
p8848
PZD receive word 5
PZD receive word 31
r8850[29]
r8860[29]
DWORD
PZD receive word 30
PZD receive word 29
r8850[28]
r8860[28]
DWORD
r8860[5]
DWORD
r8850[5]
PZD receive word 6
PROFIBUS
PROFINET
<1>
<2>
<5>
<5>
<6>
<6>
PROFIdrive sampling time
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......