2 Parameters
2.2 List of parameters
SINAMICS G130/G150
644
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note:
DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
Description:
Sets the signal source for terminal DO 1 (X481.6) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
Description:
Sets the signal source for terminal DO 2 (X481.7) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
Description:
Sets the signal source for terminal DO 3 (X481.8) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
p4031
BI: TM31 signal source for terminal DO 1 / TM31 s_src DO 1
TM31
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9549, 9556
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p4031
BI: TB30 signal source for terminal DO 1 / TB30 s_src DO 1
TB30
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9102
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p4032
BI: TB30 signal source for terminal DO 2 / TB30 s_src DO 2
TB30
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9102
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p4033
BI: TB30 signal source for terminal DO 3 / TB30 s_src DO 3
TB30
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9099, 9102
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......