SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
107
2 Parameters
2.2 List of parameters
Description:
Displays the properties supported by the power unit firmware.
Dependency:
Refer to: r0192
Description:
Displays the properties supported by the Voltage Sensing Module (VSM).
Description:
Displays the status of the components.
r0196[0]: group status of all components
r0196[1]: Status of component with component number 1
...
r0196[255]: Status of component with component number 255
r0193
Power unit firmware properties 2 / PU FW property 2
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
Component trace
Yes
No
-
06
PT1000 temperature sensor evaluation
Yes
No
-
08
Reduced undervoltage threshold during
precharging
Yes
No
-
09
Switchover to 1-phase line voltage
Yes
No
-
r0194[0...n]
VSM properties / VSM properties
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dyn. index:
p0150
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Reserved
Yes
No
-
r0196[0...255]
Topology component status / Top comp stat
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Component status bit 0
High
Low
-
01
Component status bit 1
High
Low
-
02
Component status bit 2
High
Low
-
03
Component status bit 3
High
Low
-
04
Component state
Active
Inactive/parking
-
06
Topology problem active
Yes
No
-
07
Part of the target topology
Yes
No only act topo
-
08
Alarm present
Yes
No
-
09
Safety message present
Yes
No
-
10
Fault present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
13
Maintenance required
Yes
No
-
14
Maintenance urgently required
Yes
No
-
15
Fault gone/can be acknowledged
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......