2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1016
List Manual (LH2), 07/2016, A5E03263479A
Note:
The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- article number (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9908 = 0: Component type, Article No., Hardware version, Manufacturer, Serial No.
p9908 = 1: Component type, Article Number
p9908 = 2: Component type
p9908 = 3: Component class (e.g. Sensor Module or Motor Module)
Description:
For p9909 = 1, the serial number and the hardware version of the new replaced component is automatically
transferred from the actual topology into the target topology and then saved in a non-volatile fashion.
For the components that have been replaced, the electronic rating plate must match as far as the following data is
concerned:
- component type (e.g. "SMC20")
- article number (e.g. "6SL3055-0AA0-5BA0")
For p9909 = 0, serial numbers and hardware versions are not automatically transferred. In this case, the transfer
must be made using p9904.
Dependency:
Refer to: p9904, p9905
Note:
The modified target topology is automatically saved in a non-volatile fashion when the drive object runs-up (e.g. after
a POWER ON).
Special case for Control Unit and option slot modules:
When replacing these components, independent of p9909, the serial number and hardware version are automatically
transferred and saved in a non-volatile fashion.
Description:
Accept additional inserted DRIVE-CLiQ components into the target topology.
The corresponding drive objects are added to the project.
Value:
0:
No selection
1:
Drive object type SERVO
2:
Drive object type VECTOR
3:
SINAMICS GM (DFEMV & VECTORMV)
4:
SINAMICS SM (AFEMV & VECTORMV)
5:
SINAMICS GL (VECTORGL)
6:
SINAMICS SL (VECTORSL)
p9909
Topology comparison component replacement / Topo_cmpr replace
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
Topology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
p9910
Target topology accept additional components / Add comp accept
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
C1(1)
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Topology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 6
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......