2 Parameters
2.2 List of parameters
SINAMICS G130/G150
674
List Manual (LH2), 07/2016, A5E03263479A
Description:
Display and binector output for the status for the Terminal Module 31 (TM31).
Dependency:
Refer to: p4102
Description:
Displays the temperature actual value for the Terminal Module 120 (TM120)
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
Dependency:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100 = 1, 4), the following applies:
- below the nominal response temperature, r4105 = -50°C.
- above the nominal response temperature, r4105 = 250 °C.
For sensor type "KTY84" "PT1000" (p4100 = 2, 6), the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100
Note:
r4105[0...3] = -300 °C is displayed in the following cases:
- temperature actual value invalid (F35920 ... F35923 output).
- no sensor selected (p4100[0...3] = 0).
The temperature sensor is connected to the following terminals:
X521.2(+), X521.1(-) = channel 0
X521.4(+), X521.3(-) = channel 1
X521.6(+), X521.5(-) = channel 2
X521.8(+), X521.7(-) = channel 3
Description:
Displays the temperature actual value for the Terminal Module 150 (TM150)
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
r4104.0...1
BO: TM31 temperature evaluation status / TM31 temp status
TM31
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
9549, 9576
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Alarm is present
Yes
No
-
01
Fault is present
Yes
No
-
r4105[0...3]
CO: TM120 temperature actual value / TM120 temp_act val
TM120
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8016, 9605,
9606
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2006
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
r4105[0...11]
CO: TM150 temperature actual value / TM150 temp_act val
TM150
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9626, 9627
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2006
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......