SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
839
2 Parameters
2.2 List of parameters
Description:
Selects the PZD interface for the clock cycle synchronization functionality and PROFIsafe.
Value:
1:
Interface 1 (IF1)
2:
Interface 2 (IF2)
Index:
[0] = Isochronous mode
[1] = PROFIsafe
Dependency:
Refer to: p8839
Note:
A change only becomes effective after POWER ON, reset or project download.
Example:
p8815[0] = 1: IF1 supports the isochronous mode.
p8815[1] = 2: IF2 supports PROFIsafe.
Description:
Sets the number of remote controllers expected for PROFINET CBE20/CBE25.
The "Shared Device" functionality is activated with a value = 2.
The drive is being accessed by two PROFINET controllers simultaneously:
- automation controller (SIMOTION or SIMATIC A-CPU).
- safety controller (SIMATIC F-CPU).
Value:
1:
Automation or Safety
2:
Automation and Safety
Notice:
The F CPU may only use PROFIsafe telegrams.
The A CPU must be connected to enable the F CPU to gain access.
Set the value = 1 to commission the F CPU individually.
Note:
A change only becomes effective after a POWER ON.
Description:
Selects the firmware version for the CBE20.
Value:
1:
PROFINET Device
2:
PROFINET gate
3:
SINAMICS Link
4:
EtherNet/IP
5:
Modbus TCP
99:
Customer-specific from the OEM directory
p8815[0...1]
IF1/IF2 PZD functionality selection / IF1/IF2 PZD fct
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 2
1
p8829
CBE2x remote controller number / CBE2x rem ctrl num
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 2
1
p8835
CBE20 firmware selection / CBE20 FW sel
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2197, 2198
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 99
1
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......