987
2 Parameters
2.2 List of parameters
For index 1:
- for a 2-encoder system with non safety-capable encoders, this means the poorer value for both encoders. Index[1]
takes into account the coarse resolution of the encoder only
Internal calculation, which also incorporates the factor for the motor-load side conversion, the gearbox ratio and the
safety monitoring clock cycle. Result returns mm/min (linear) or rpm (rotary).
- for safety without encoder, index 1 is not relevant, and is always the value of zero.
Description:
Displays the necessary setpoint speed limit as a result of the selected motion monitoring functions.
Contrary to the parameterization of the SI limit values, this parameter specifies the motor-side limit value and not the
load-side limit value.
Recommendation:
For the ramp-function generator, by appropriately interconnecting the speed limits p1051 and p1052 with r9733[0, 1],
a drive-based setpoint velocity limiting can be realized.
- CI: p1051 = r9733[0]
- CI: p1052 = r9733[1]
Additional limiting can also be activated using connector input p1085 and p1088.
Index:
[0] = Setpoint limiting positive
[1] = Setpoint limiting negative
[2] = Setpoint limit absolute
Dependency:
For SLS: r9733[0] = p9531[x] x p9533 (converted from the load side to the motor side)
For SDI negative: r9733[0] = 0
For SLS: r9733[1] = - p9531[x] x p9533 (converted from the load side to the motor side)
For SDI positive: r9733[1] = 0
[x] = Selected SLS stage
Conversion factor from the motor side to the load side:
- motor type = rotary and axis type = linear: p9522 / (p9521 x p9520)
- otherwise: p9522 / p9521
Refer to: p9531, p9533
Notice:
If p1051 = r9733[0] is interconnected, p1052 = r9733[1] must also be interconnected and vice versa.
If only the absolute value of the setpoint velocity limiting is required, r9733[2] must be interconnected.
Note:
The unit changeover between linear and rotary axis is not implemented via the safety changeover (p9502) but by the
linear motor changeover.
If the "SLS" or "SDI" function is not selected, r9733[0] shows p1082 and r9733[1] shows -p1082.
The display in r9733 can be delayed by up to one Safety monitoring clock cycle as compared to the display in
r9719/r9720 and r9721/r9722.
Description:
Display and BICO output for status word S_ZSW1B of the safety information channel.
r9733[0...2]
CO: SI Motion setpoint speed limit effective / SI Mtn setp_lim
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2820, 2824,
3630
P-Group:
Safety Integrated
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r9734.0...15
CO/BO: SI Safety Info Channel status word S_ZSW1B / SIC S_ZSW1B
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
STO active
Yes
No
-
01
SS1 active
Yes
No
-
02
SS2 active
Yes
No
-
03
SOS active
Yes
No
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......