SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
681
2 Parameters
2.2 List of parameters
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4105, p4111, r4112, r4113, p4122
Description:
Sets the rated line frequency for the filter to skip the line frequency for Terminal Module 150 (TM150).
Value:
0:
50 Hz
1:
60 Hz
Description:
Sets the smoothing time constant for the 1st order lowpass filter of the temperature channels.
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
In order that the value becomes effective, p4122 must be set >= 2 *channel sampling time.
The following applies:
Channel sampling time = active number of channels * 50ms
For lower values, a smoothing of 2 * channel sampling time.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4120
Description:
Sets the sensor type of the first temperature sensor for the motor temperature monitoring.
Value:
0:
No sensor
10:
PTC fault
11:
PTC alarm
12:
PTC alarm & timer
20:
KTY84
30:
Bimetallic NC contact fault
p4121
TM150 filter rated line frequency / TM150 filt f_line
TM150
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9626, 9627
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p4122[0...11]
TM150 smoothing time constant / TM150 T
TM150
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
9626, 9627
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
100 [ms]
10000 [ms]
100 [ms]
p4600[0...n]
Motor temperature sensor 1 sensor type / Temp_sens 1 type
VECTOR_G
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
EDS, p0140
Func. diagram:
8016
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 60
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......