2 Parameters
2.2 List of parameters
SINAMICS G130/G150
468
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the valve lockout time to compensate for phase U.
Notice:
Deadtime compensation is deactivated with p7003 = 2.
Note:
The value is automatically calculated in the motor data identification routine.
For type PM340 power units, the value is limited to 3.98 µs.
Description:
Sets the valve lockout time to compensate for phase V.
Notice:
Deadtime compensation is deactivated with p7003 = 2.
Note:
For type PM340 power units, the value is limited to 3.98 µs.
Description:
Sets the valve lockout time to compensate for phase W.
Notice:
Deadtime compensation is deactivated with p7003 = 2.
Note:
For type PM340 power units, the value is limited to 3.98 µs.
Description:
Sets the current level for the dead time compensation.
Above the current level, the dead time - resulting from the converter switching delays - is compensated by a
previously calculated constant value. If the relevant phase current setpoint falls below the absolute value defined by
p1832, the corrective value for this phase is continuously reduced.
Dependency:
The factory setting of p1832 is automatically set to 0.02 * rated drive converter current (r0207).
p1828
Compensation valve lockout time phase U / Comp t_lock ph U
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
p1829
Compensation valve lockout time phase V / Comp t_lock ph V
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
p1830
Compensation valve lockout time phase W / Comp t_lock ph W
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
p1832
Dead time compensation current level / t_dead_comp I_lev
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Modulation
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Arms]
10000.0 [Arms]
0.0 [Arms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......