SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
587
2 Parameters
2.2 List of parameters
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency:
Refer to: p2900, p2901, p2930
Note:
The signal sources can, for example, be used to interconnect scalings.
Description:
Setting and connector output for a fixed torque value.
Dependency:
Refer to: p2900, p2901, r2902
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can, for example, be used to interconnect a supplementary torque.
Description:
Displays the values of the direct access flux model for the synchronous reluctance motor (RESM) for diagnostic
purposes.
Valid values are only displayed when the pulses are inhibited.
For index 0:
Display of the entered direct axis current id in Arms:
For index 1, 2, 3:
Display of the saturation curves of the direct axis flux psid(id, iq):
- r2969[1]: flux in Vsrms with respect to the direct axis current for iq = 0
- r2969[2]: flux in Vsrms with respect to the direct axis current for iq = 0.5* p2950
- r2969[3]: flux in Vsrms with respect to the direct axis current for iq = p2950
For index 4, 5, 6:
Displays the relative error of the current inversion (id(psid, iq) - id) / p2950:
- r2969[4]: error with respect to direct axis current for iq = 0
- r2969[5]: error with respect to direct axis current for iq = 0.5 * p2950
- r2969[6]: error with respect to direct axis current for iq = p2950
Index:
[0] = d-current
[1] = d-flux iq0
[2] = d-flux iq1
[3] = d-flux iq2
[4] = d-current error iq0
[5] = d-current error iq1
[6] = d-current error iq2
Note:
RESM: reluctance synchronous motor (synchronous reluctance motor)
p2930[0...n]
CO: Fixed value M [Nm] / Fixed value M [Nm]
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
1021
P-Group:
Setpoints
Unit group:
7_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
p2003
Expert list:
1
Min Max
Factory
setting
-100000.00 [Nm]
100000.00 [Nm]
0.00 [Nm]
r2969[0...6]
Flux model value display / Psi_mod val displ
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, PMSM, SESM,
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......