2 Parameters
2.2 List of parameters
SINAMICS G130/G150
574
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2252, p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
Note:
Limiting only active for p2252.3 = 1.
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2252, p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value falls below this lower limit, this results in fault F07426.
Note:
Limiting only active for p2252.3 = 1.
Description:
Sets the scaling factor for the actual value of the technology controller.
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2271
Note:
For 100%, the actual value is not changed.
Description:
Setting to use an arithmetic function for the actual value signal of the technology controller.
Value:
0:
Output (y) = input (x)
1:
Root function (root from x)
2:
Square function (x * x)
3:
Cube function (x * x * x)
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2269, p2271
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
9_1
Unit selection:
p0595
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-10000.00 [%]
10000.00 [%]
200.00 [%]
p2268
Technology controller lower limit actual value / Tec_ctrl l_lim act
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
9_1
Unit selection:
p0595
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-10000.00 [%]
10000.00 [%]
-200.00 [%]
p2269
Technology controller gain actual value / Tech_ctrl gain act
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
500.00 [%]
100.00 [%]
p2270
Technology controller actual value function / Tec_ctr ActVal fct
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......