SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
83
2 Parameters
2.2 List of parameters
Description:
Displays the activated function module for the particular drive object.
Dependency:
Refer to: p0171, r0171, p0172, r0172, p0173, r0173
Note:
A "function module" is a functional expansion of a drive object that can be activated when commissioning.
Description:
Displays the activated function module for the particular drive object.
Dependency:
Refer to: p0171, r0171, p0172, r0172, p0173, r0173
Note:
A "function module" is a functional expansion of a drive object that can be activated when commissioning.
Description:
Displays the basic sampling times.
The sampling times are set using p0112 and p0115. The values for the basic sampling times are determined as a
result of these settings.
Index:
[0] = Basic sampling time 0
[1] = Basic sampling time 1
[2] = Basic sampling time 2
Description:
Displays the selected basic sampling time for this drive object.
Dependency:
Refer to: r0110
r0108
Drive objects function module / DO fct_mod
TM31, TM120, TM150,
TB30
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
18
Free function blocks / FBLOCKS
Activated
Not activated
-
31
PROFINET CBE20 / PN CBE20
Activated
Not activated
-
r0108
Drive objects function module / DO fct_mod
ENC
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
12
Linear encoder / Lin_enc
Activated
Not activated
-
18
Free function blocks / FBLOCKS
Activated
Not activated
-
31
PROFINET CBE20 / PN CBE20
Activated
Not activated
-
r0110[0...2]
Basic sampling times / t_basis
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [µs]
- [µs]
- [µs]
r0111
Basic sampling time selection / t_basis sel
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP,
VECTOR_G, B_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......